Technical Specifications for Water Cooled Jumpers

Installation Methods
Water-cooled jumpers should always be installed with a bend radii ranging from 90° to 180°.

Jumper Bend Specificationsfor Water-Cooled Type

Recommended Minimum
Bend Radii:
350 MCM - 400 MCM ... 2"
500 MCM - 600 MCM ... 3"
750 MCM - 1000 MCM ... 4"
Minimum Distance from the End of the Hose to the Point Where the Bend Radii Should Start is
as Follows:
350 MCM - 400 MCM ... 2 1/2"
500 MCM - 600 MCM ... 3"
750 MCM - 1000 MCM ... 3 1/2"

It should be pointed out that the jumper life is inversely proportional to its operating temperature; the higher the temperature the shorter the life.

The recommended operating temperature is 55°C or less, but the maximum allowable operating temperature should not exceed 70°C.

Sufficient water flow to insure a low operating temperature is very important.

 

General Information & Technical Data

MCM DC Resistance
(Ohms per ft. at 70_C)
350 .0000376
400 .0000322
500 .0000263
600 .0000217
750 .0000172
1000 .0000130
1200 .0000110
1500 .0000088
2000 .0000066


Click Thumbs Below
for isometric drawings
and detailed information

type b specifications
Type B

type b-2 specifications
Type B-2

type b-4 specifications
Type B-4

type b-5 specifications
Type B-5

type b-6 specifications
Type B-6

type b-6 2 hole specifications
Type B-6 (2 hole)

type b-7 specifications
Type B-7

type b-9 specifications
Type B-9

type b-11 specifications
Type B-11

©2005 Watteredge, Inc. 567 Miller Road, Avon Lake, Ohio 44012-2304 USA
P:440-933-6110 F:440-933-8248
site map | links | home