Technical Specifications for Water Cooled Jumpers

Installation Methods

Water cooled jumpers should always be installed with a bend angle ranging from 90° to 180°.

Jumper Bend Specificationsfor Water Cooled Type

Recommended minimum
Bend angle:
350 MCM - 400 MCM ... 2”
500 MCM - 600 MCM ... 3”
750 MCM - 1000 MCM ... 4”
Minimum distance from the end of the hose to the point where the bend angle should start is as follows:
350 MCM - 400 MCM ... 2 1/2”
500 MCM - 600 MCM ... 3”
750 MCM - 1000 MCM ... 3 1/2”

It should be pointed out that the jumper life is inversely proportional to its operating temperature; the higher the temperature the shorter the life.

The recommended operating temperature is 55°C or less, but the maximum allowable operating temperature should not exceed 70°C.

Sufficient water flow to insure a low operating temperature is very important.

General Information & Technical Data

MCMDC Resistance
(Ohms per ft. at 70°C)
350 .0000376
400 .0000322
500 .0000263
600 .0000217
750 .0000172
1000 .0000130
1200 .0000110
1500 .0000088
2000 .0000066